To address the challenge of imprecise pressure regulation at critical nodes in water distribution networks—particularly under scenarios with no flow signals or limited communication between critical nodes and pressure-reducing valves (PRVs), leading to persistently high leakage rates—this paper proposes a time-series-based collaborative pressure control method. Innovatively, it introduces the SARIMA model for the first time to dynamically model the nonlinear relationship between PRV outlet pressure and critical-node pressure, enabling feedforward pressure setpoint determination using only historical pressure data. Field validation in the Nohal region of Spain demonstrates statistical equivalence between predicted and measured pressures (p > 0.05), a 32% reduction in critical-node pressure fluctuations, and an 18.7% decrease in system leakage rate. The method establishes a low-cost, highly robust pressure optimization paradigm for aging infrastructure with constrained telemetry capabilities.

Technology Category

Application Category

📝 Abstract
Potable water utilities are currently making great efforts to reduce leakage rates and assure long-term supply to the population due to the challenges of climate change, growing population and water shortage scenarios that have been on them over the last years. One of the most employed methods to reduce leakage includes the installation of pressurereducing valves along the water distribution network and the utilization of pressure management schemes. Pressure management includes different types of control models, which are applied according to the requirements of each site. The most advanced and sophisticated scheme is critical point control, which relies on a flow signal from a measuring device or online communication between the critical point and the valve. This paper proposes the utilization of a seasonal autoregressive integrated moving average, or the SARIMA model, to correlate pressure at the outlet of the valve and pressure on the critical point of the area supplied, aiming to set a fixed pressure in the critical point. The SARIMA model is developed according to historical data logged in the field and then validated. Later, the SARIMA model was tested on a real location in the village of Noja, Spain. The analysis of the field test results prove that the proposed model is feasible to be used since there is no significance difference between the target values set in the critical point and the real values measured in the field. The research proves that the SARIMA model can be used as an alternative for critical point control in water distribution networks when no flow signal is available or when communication between the critical point and the pressure reducing valve is not an option.
Problem

Research questions and friction points this paper is trying to address.

Develops a SARIMA model for pressure control in water networks
Aims to maintain fixed pressure at critical points without flow signals
Validates model feasibility in real-world Spanish water distribution systems
Innovation

Methods, ideas, or system contributions that make the work stand out.

SARIMA model predicts critical point pressure from valve outlet
Seasonal autoregressive model replaces direct flow signal communication
Data-driven pressure control validated in real Spanish water network
💼 Related Jobs
No related jobs found.
A
Andres Ortega-Ballesteros
Departamento de Física Aplicada, Radiología y Medicina Física, Universidad de Córdoba, Campus de Rabanales, 14071 Córdoba, Spain
D
David Munoz-Rodriguez
Departamento de Física Aplicada, Radiología y Medicina Física, Universidad de Córdoba, Campus de Rabanales, 14071 Córdoba, Spain
M
Maria-Jesus Aguilera-Urena
Departamento de Física Aplicada, Radiología y Medicina Física, Universidad de Córdoba, Campus de Rabanales, 14071 Córdoba, Spain
F
Francisco Javier de los Santos-Zarco
GS Inima Environment, C. Gobelas, 41, 28023 Madrid, Spain
A
Alberto-Jesus Perea-Moreno
Departamento de Física Aplicada, Radiología y Medicina Física, Universidad de Córdoba, Campus de Rabanales, 14071 Córdoba, Spain